with a voltage-controlled sheath is typically used as an isolated down conductor in the field of lightning protection for control the separation distance according to IEC 62305-3
There is a risk of uncontrolled flashover between parts of external lightning protection system and electrical installations in the building if the distance between the air termination system or down conductor and metal, electrical installations in the structure requiring protection is not sufficient. The separation distance is calculated according to IEC 62305-3. Advantage of KHV cable is the decrease of separation distance.
KIC Cable conductor has a copper core and high voltage resistant XLPE insulation. The area at risk of touch voltages for persons outside a building is located within a distance of 3 m. around the down conductor and at a height of 3 m from ground level. The insulation of down-conductor is tested by a 100 kV, 1.2/50 impulse withstand voltage shall be adopted for protect dangerous of touch voltage.